SECONDARY TEST SET

Trip Test Sets for a Wide Variety of Circuit Breakers

ABB EKIP T&P
  • Monitor The State Of The Circuit-Breakers Connected And Record Information
  • Execute Operations, Resets, Signaling, Etc
  • Configure The Protection Releases With Customized Parameters
  • Download Information From Releases Equipped With Data Logger
Data Sheet
ABB PR010/T
  • Capable Of Performing The Functions Of Testing, Programming And Reading Parameters For The Protection Units Equipping ABB SACE Low-Voltage Circuit-Breakers
  • The ABB PR010/T Tests Protection Units By Monitoring Both Their HW And SW Component
Data Sheet
ALLEN BRADLEY 140G-ELBU
  • 140GELBU
  • Circuit Breaker Accessory
  • Frame-N
  • Battery Unit
Data Sheet
ALLEN BRADLEY 140G-ELTT
  • Allen-Bradley 140G-ELTT Trip Test Unit Features:
  • Padlocking Hasp
  • Lock-OFF Only
  • Standards: UL489, CSA22.2 Number 5, IEC 60947-2, CE, CSA Certifed, UL Listed
Data Sheet
EATON / CUTLER HAMMER - DS & DSII ADAPTER, 8779C02G03
  • Will Enable The 140D481G03 Test Set To Test DS Breakers With Digitrip Trip Units Manufactured After May 1993
  • DSII Air Circuit Breakers Are Equipped With The New Test Port
Data Sheet
EATON / CUTLER HAMMER - MAGNUM ADAPTOR, 8779C02G04
  • For Magnum DS Digitrip Trip Units
  • Converts The 11-Pin Banana Plug On Test Kit To A14-Pin Plug
  • 14 Pin Plug Required To Plug Into The Trip Test Unit Test Port Located On The Face Of The Trip Unit
Data Sheet
EATON / CUTLER HAMMER , 1287C56G02 (SELTRONIC, STK2)
  • Used For Testing Digitrip310 Trip Units
  • CAT STK2 Seltronic Secondary Injection Test Set
  • For Seltronic And Series C Circuit Breakers
Data Sheet
EATON /CUTLER HAMMER - MTK2000
  • Test And Verify The Pickup Levels And Time Delay Settings Of A Breaker’s Trip Unit
  • 520Digitrip Units: Supports The 520 Curves Accept The Short Delay I2T And Ground I2T
  • 1150Digitrip Units: Does Not Support The Long Delay I4T Short Delay Flat Curve
Data Sheet
EATON 70C1056
  • Can Test The Digitrip 520, 520i, 520M, 520Mi, 520MC And 520MCi
  • In Addition They Can Test The Digitrip1150 Family Consisting Of The Digitrip 1150, 1150i, The Digitrip 1150V And 1150Vi, And The Digitrip 1150+ And 1150i+ By Overlaying A Nameplate On The Tester
Data Sheet
Eaton 140D481G03( Amptector)

The Eaton Cutler Hammer 140D481G03 Secondary Injection Test Set is used to test and verify the pickup levels and time delay settings of a breaker’s Trip Unit

The 140D481G03 is used to test Amptector, Digitrip, RMS or Optim Trip Units

Data Sheet
Eaton Digitrip Optimizer
  • EATON Breaker Hand Held Programmer, For Use With: OPTIM 550/750/1050 Electronic Trip Unit
  • Plug in mount
  • Monitor/display parameters, configure setting function

Data Sheet
FEDERAL PIONEER DDT-USD
  • Battery Powered, Portable Test Unit
  • Field Testing Of Type USR And USRC Family Of Overcurrent Relays
  • Can Be Used As A Stand Alone Or As A Component Of The Air Circuit Breaker
Data Sheet
FEDERAL PIONEER DDT-USRC
  • Operation From A 100-240VAC 50/60 Hz
  • Provides Power To The Trip Unit For Viewing And Setting Set- Points With Less Than 15% Load On The Breaker Or If The Replaceable Trip Unit Battery Needs Replacing
  • Verification Of Metering (Phase Simulation)
  • Ground Fault Testing With Ground Fault Trip Indication
  • Temporarily Disable The Ground Fault Feature During Single Phase Breaker Testing
Data Sheet
GE TVRMS 2
  • Operation From 120 Vac Orsix D-Cell Batteries.
  • Trip Unit Testing Without De-Energizing The Breaker Or Removing The Trip Unit From The Breaker.
  • Verification Of Switch Settings On Power+, RMS-9 And Epic Trip Units
Data Sheet
GE GTUTK20
  • Operation From A 100-240VAC 50/60 Hz
  • Provides Power To The Trip Unit For Viewing And Setting Set- Points With Less Than 15% Load On The Breaker Or If The Replaceable Trip Unit Battery Needs Replacing
  • Verification Of Metering (Phase Simulation)
  • Ground Fault Testing With Ground Fault Trip Indication
  • Temporarily Disable The Ground Fault Feature During Single Phase Breaker Testing
Data Sheet
SCHNEIDER / MERLIN GERIN 34547 (MASTERPACT STR)
  • Test A Sequence Of Settings For The Schneider Masterpact STR, Compact STRF And NS Range Circuit Breakers Via The Front-End Connector
  • NSX Maintenance Module Can Test For Thermal Protection Trip And Time, Instantaneous Trip And Ready LED Function Check
  • Can Supply The 24Vrequired To Power Breaker Independently
Data Sheet
SCHNEIDER S33595
  • Operation From 120 Vac Orsix D-Cell Batteries.
  • Trip Unit Testing Without De-Energizing The Breaker Or Removing The Trip Unit From The Breaker.
  • Verification Of Switch Settings On Power+, RMS-9 And Epic Trip Units
  • The Square D Function Test Kit Designed To Perform Tests On Micrologic, NT And STR Trip Units.
  • Zone-Selective Interlocking Test
  • Ground-Fault Inhibit
  • Thermal-Imaging Inhibit
Data Sheet
SCHNEIDER STRV00910 (UTA TEST KIT)
  • Test A Sequence Of Settings For The Schneider Masterpact STR, Compact STRF And NS Range Circuit Breakers Via The Front-End Connector
  • NSX Maintenance Module Can Test For Thermal Protection Trip And Time, Instantaneous Trip And Ready LED Function Check
  • Can Supply The 24Vrequired To Power Breaker Independently
Data Sheet
SCHNEIDER UTS-3
  • Perform Operational Tests And Diagnosis Of Square D Micrologic Series B Electronic Trip Units On Circuit Breakers
  • Includes Rating Plug Adapter
Data Sheet
SIEMENS EPSP18V VL (POWERSTICK DG-PG)
  • Siemens Breaker Power Stick For Use With LCD Trip Unit
  • Handheld Unit
  • Battery Powered (Two 9VDC Batteries)
Data Sheet
SIEMENS PTS-5
  • Testing Of The Static Trip III (STIII) Overcurrent Tripping System Utilized On The RL Breaker
  • Self-Contained Brief Case, Requiring 120VAC To Operate
  • Microprocessor Controlled Constant Current Source Which Enables Rapid Verification
Data Sheet
SIEMENS PTS4
  • Input - 120 Volts, 50 Or 60 Hz, 15 Amps Maximum
  • Output - 0 To 120 Volts, 15 Amps Maximum
  • Maximum Continuous Current On High Scale 1.0 Amp
  • Maximum Continuous Current On Low Scale 0.75 Amp
  • DC Output For Actuator Test - 0 To 22 Volts Open Circuit
Data Sheet
SIEMENS TS-31
  • Testing Of The Static Trip III (STIII) Overcurrent Tripping System Utilized On The RL Breaker
  • Self-Contained Brief Case, Requiring 120VAC To Operate
  • Microprocessor Controlled Constant Current Source Which Enables Rapid Verification
Data Sheet
SIEMENS WLTS
  • The Siemens WLTS Is A Test Device For WL Breaker Electronic Trip Units (ETU)
  • Handheld Device Is Used To Verify The Proper Operation Of The Trip Unit, The Energy Transformers And Current Transformers As Well As The Tripping Solenoid F5 And The Measured Value Display
Data Sheet
URC B291 AC-PRO-MP
  • The Utility Relay Co. B-291-MP Secondary Injection Test Set Is A Single-Phase Test Set Specifically Designed For Testing The Operation Of The AC-PRO-MPTM Microcontroller Based Trip Units Manufactured By Utility Relay Co
  • The AC-PRO-MP Is A Plug-In, Direct Replacement Trip Unit For The STR Trip Units On The Merlin Gerin & Square D Masterpact MP Breakers
Data Sheet
URC B292 AC-PRO
  • The Utility Relay Co. B-292 Secondary Injection Test Set Is A Single-Phase Test Set Specifically Designed For Testing The Operation Of The AC-PRO And AC-PRO-II Microcontroller Based Trip Units Manufactured By Utility Relay Co
  • Test Pick-Up And Time Delays Of The Various Protection Functions By Driving Current Into The Trip Unit On The Secondary Side Of The CT Circuit
  • Test Set Will Test 60, 50, 40 Or 25 Hertz AC-PRO® Trip Units
Data Sheet

Request Quote

Lets us help you find the right equipment for the job.

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.

Visit Us

Come by the office anytime during working hours.